MMG 80 Mobile Generator

Specifications

Output

3 Phase - Standby (kw / kva) 68 / 85
Amps (480 / 208V) 102 / 236
3 Phase - Prime (kw / kva) 64 / 80
Amps (480 / 208V) 96 / 222
1 Phase - Standby (kw / kva) 60 / 60
Amps (240V) 250
1 Phase - Prime (kw / kva) 55 / 55
Amps 229
AC Voltage 1-phase 120,139,208,220,240,277
AC Voltage 3-phase 208, 220, 440, 480
Frequency Hz. 60
Power Factor 1.0 (1 Phase) / .8 (3 Phase)
Generator (Brand / Type / Insulation) Marathon / Brushless / H
Sound (dB9(A) 23 Feet @ prime) 68

Size and Weight

Skid Mounted (l x w x h) 96 x 38 x 61.5
Dry Weight lb. (kg.) 3240 (1470)
Operating Weight lb. (kg.) 4210 (1910)
Trailer Mounted (l x w x h) (in.) 158 x 60 x 83.5
Dry Weight lb. (kg.) 3490 (1790)
Operating Weight lb. (kg.) 4910(2230)

Engine

Type Tier II- Flex Engine
Brand John Deere
Aspiration Turbo
Hp (prime @ 1800rpm) (kWm) 102 (76)
Displacement C.I.D. (l.) 274 (4.5)
Cylinders 4
Speed (rpm) 1800
Fuel Consumed (prime gal. (l.)/h) 5.6 (21.3)
Battery (12 volt) 1 - 12V / 720 CCA wet cell

Capacities

Fuel Tank gal. (l.) 135 (511)
Approximate Run Time (hrs.) 24
Coolant (qt.) (l.) 19.5 (18.5)
Oil qt. (l.) 9 (8.5)

AC Distribution

Main Breaker 300
Voltage Selection 3 Position Switch (Lockable)
Voltage Regulation +/-1%
120V - 20 amp GFI Duplex 2
240V - 20 amp Twist Lock NA
240V - 50 amp Twist Lock 3

Trailer

Number of Axles & Capacity (lbs.) 1 (6000)
Tire Size (in.) 15
Brakes Surge
Hitch Adjustable 2" Ball or 3" Ring

Options

Engine In-line engine block heater, 720 CCA gel cell battery, 900 CCA wet cell battery, Lockable battery disconnect, 36 hr. fuel tank; no containment; req. tandem trailer, 24 hr. fuel tank; no containment; no foam, 24 hr. fuel tank; 120% containment, 36 hr. fuel tank; 120% containment; req.tandem trailer, 24 hr. fuel tank; 120% containment; no foam, 30 hr. fuel tank; double wall; no containment, Fuel transfer pump
Generator Stnd. Generator - 4 position phase switch, Stnd. generator - dedicated 120/208 VAC, PMG generator - 3 position phase switch, PMG generator - 4 position phase switch, PMG generator - dedicated 120/208 VAC, Super start generator- 3 position phase switch-req. tandem trailer, Super start generator- 4 position phase switch-req. tandem trailer, Super start generator - dedicated 120/208 VAC-req. tandem trailer
Unit Low coolant shutdown kit, Analog gauges
Electrical Buck Transformer - 120v @ 480VAC, Auxilliary strobe /audible indication, Control panel light, Interior light, 2 amp trickle battery charger
Enclosure Fire extinguisher
Trailer Single axle w/ electric brakes, Tandem axle w/ electric brakes, Tandem axle w/ surge brakes, Adjustable height 2"'or 2 5/16" ball , 6 pole or 7 pole electrical connectors, Spare tire / wheel kit ( single or tandem) ,